Mini Chiller
Model name | ¡¡ | ACMI-H12/4 | ACMI-H16/5 | ACMI-H28/5 | ACMI-H42/5 | |
Capacity | Cooling | Btu/h | 44500 | 54500 | 97500 | 14500 |
kW | 13.0 | 16.1 | 28.5 | 42.5 | ||
Heating | Btu/h | 49000 | 60500 | 104000 | 158500 | |
kW | 14.3 | 17.7 | 30.4 | 46.5 | ||
Electric Data | Power Supply | V~,Hz,Ph | 220~240,50,1 | 380~415,50,3 | 380~415,50,3 | 380~415,50,3 |
Cooling Power Input | kW | 4.48 | 5.60 | 9.80 | 14.40 | |
Heating Power Input | kW | 4.70 | 5.80 | 10.00 | 15.00 | |
Cooling Current | A | 22.7 | 10.6 | 18.3 | 26.2 | |
Heating Current | A | 22.8 | 10.7 | 18.1 | 27.4 | |
Compressor | Type | ¡¡ | Scroll | Scroll | Scroll | Scroll |
Quantity | Pieces | 2 | 2 | 2 | 2 | |
Refrigerant Type | ¡¡ | R22 | R22 | R22 | R22 | |
Air Side Heat Exchanger | Type | ¡¡ | Copper tube-fin coil | Copper tube-fin coil | Copper tube-fin coil | Copper tube-fin coil |
Fan Quantity | Pieces | 2 | 1 | 2 | 2 | |
Air Flow Volume | m3/h | 5600 | 7200 | 12000 | 18500 | |
Water Side Heat Exchanger | Type | Plate heat exchanger | Plate heat exchanger | Plate heat exchanger | Plate heat exchanger | |
Water Resistance | kPa | 50 | 54 | 54 | 60 | |
Water Flow Volume | m3/h | 2.24 | 2.77 | 4.90 | 7.31 | |
Max. Pressure | MPa | 1 | 1 | 1 | 1 | |
Water Pump Head | ¡¡ | 16 | 22 | 23 | 22 | |
Water Pump Input | W | 290 | 580 | 940 | 910 | |
Dimension(W¡ÁD¡ÁH) | Net | mm | 1160¡Á560¡Á1260 | 1000¡Á660¡Á1800 | 1600¡Á660¡Á1800 | 1950¡Á660¡Á1800 |
Packing | mm | 1280¡Á640¡Á1450 | 1140¡Á780¡Á1990 | 1800¡Á780¡Á1990 | 2090¡Á780¡Á1990 | |
Weight | Net | kg | 192 | 250 | 360 | 508 |
Gross | kg | 205 | 265 | 375 | 520 | |
Inlet/Outlet Water Pipe | mm | DN25 | DN32 | DN40 | DN40 | |
Noise | dB(A) | ¡Ü60 | ¡Ü61 | ¡Ü63 | ¡Ü67 | |
Safety Protection | Hi/low pressure /water flux/over heating/over current/lack-phase/anti-phase protection |
Note:
All the above data is measured base on the following working condition:
Rated cooling working condition: water flow 0.172 m3/(h•kW), chilled water inlet/outlet temperature 12¡æ/7¡æ, ambient temperature 35¡æ;
2.Rated heating working condition: water flow 0.172 m3/(h•kW), hot water inlet/outlet temperature 40¡æ/45¡æ, ambient temperature 7¡æ, WB temperature 6¡æ;
. Keep 1m away from the chiller front and 1.5m high when detecting noise level, environmental noise is lower than 30db(A);
As a part of continuous product improvement, we reserves the right to change specifications without notice